Dbnd – insensitivity range (dead band) – Burkert Type 8793 User Manual
Page 94
94
Start-Up
25.3.2.
DBND – Insensitivity range (dead band)
This function causes the process controller to respond from a specific control difference only. This protects both
the solenoid valves in Type 8792/8793 and the pneumatic actuator.
Factory setting: 1.0 % with reference to the range of the scaled process actual value
(setting in the menu
PV-SCALE → PVmin → PVmax).
Operating structure:
EXIT
Input value
ENTER
INPUT
OK
ESC
PID.PARAMETER
DBND 1.0 %
FILTER 0
Figure 43:
Operating structure DBND; insensitivity range
Insensitivity range for process control
Process
set-point value
(SP)
Control
difference
Xd2
Process
actual value
(PV)
Xd2
Xd2‘
Xd2‘
to the controller
Dead band
Figure 44:
Diagram DBND; insensitivity range for process control
25.3.3.
KP – Amplification factor of the process controller
The amplification factor specifies the P-contribution of the PID controller
(can be set with the aid of the
P.TUNE function).
Factory setting: 1.00
Operating structure:
EXIT
Input value
ENTER
INPUT
OK
ESC
PID.PARAMETER
KP 1.00
FILTER 0
DBND 1.0 %
Adjustment range: 0 ... 99.99
(% / set unit)
Figure 45:
Operating structure KP; amplification factor
The
KP amplification of the process controller refers to the scaled, physical unit.
English
Type 8792, 8793