Burkert Type 8793 User Manual
Page 131

131
Auxiliary functions
• Safepos.-.Outputting.the.message:.Actuator.in.safety.position
• ERR.SP/CMD.-.Outputting.the.message:.Sensor.break.for.process.set-point.value/set-point.position.
Only available if the function in the
SIG.ERR menu has been activated (SIG.ERR → SP/CMD input → Error on).
See Chapter “26.2.12. SIG.ERROR – Configuration of signal level fault detection”.
• ERR.PV -.Outputting.the.message:.Sensor.break.for.process.actual.value.(only.for.Type.8793).
Only available if the function in the
SIG.ERR menu has been activated (SIG.ERR → PV Input → Error on).
See Chapter “26.2.12. SIG.ERROR – Configuration of signal level fault detection”.
• Remote.-.Output.AUTOMATIC./.MANUAL.operating.state
• Tune.Status -.Output.TUNE.(process.optimization)
Key
Action
Description
/
Select submenu option
(Safepos, ERR.SP/CMD, ERR.PV, Remote or Tune.Status).
SELEC
Press
Acknowledge submenu option as output function for the binary
output. The selection is marked by a filled circle .
Then set the required switching status in the
OUT.type submenu.
Table 60:
OUT BIN1 / OUT BIN2; specifying Safepos, ERR.SP/CMD, ERR.PV, Remote or Tune.Status as output.
• DIAG.State-1/2.-.Diagnosis.output.(option).
Outputting.the.message:.Diagnosis.message.from.selected.status.signal.
For description see Chapter “26.2.22. DIAGNOSE – Menu for monitoring valves (option)”.
Key
Action
Description
/
Select
DIAG.State-1/2
SELEC
Press
The status signals, which can be activated for outputting the
message, are displayed.
/
Select status signal
Select the status signal which is to be assigned to the diagnosis
output.
SELEC
Press
Activate the selection by checking the box or deactivate it by
unchecking the box .
If required, activate further status signals for the diagnosis output by
pressing the / and
SELEC
keys.
EXIT
Press
Acknowledgment and simultaneous return to the
OUT BIN 1/2 menu.
Then set the required switching status in the
OUT.type submenu.
Table 61:
OUT.type; inputting switching status for binary output and return to the process level.
english
Type 8792, 8793