beautypg.com

Burkert Type 8793 User Manual

Page 163

background image

163

Auxiliary functions

Key

Action

Description

/

Increase value

<

Changing the decimal

place

Input upper temperature limit

TEMP.MAX.

OK

Press

Acknowledge value.

/

Select

TEMP.MIN

INPUT

Press

Open factory setting for lower temperature limit.

/

Increase value

<

Changing the decimal

place

Input lower temperature limit

TEMP.MIN.

OK

Press

Acknowledge value.

EXIT

Press

Return to the

TEMP.CHECK menu.

EXIT

Press

Return to the

DIAGNOSE main menu.

Table 89:

TEMP.CHECK; specifying temperature limit.

STROKE.CHECK –.End.position.monitor

The

STROKE.CHECK function is used to monitor the physical end positions of the armature. In this way wear marks

can be detected on the valve seat.

To do this, a tolerance band is specified for the lower end position (position 0 %) and for the upper end position
(position 100 %). If an end position exceeds or falls below the tolerance band, a message is output.

• To do this, a history entry is made in the

HISTORY submenu. For description see “26.2.22.7. History entries in

the HISTORY submenu”.

• The status signal, which is assigned to the message, is indicated at short intervals on the display.

See also

D.MSG and CONFIG.MSG in Chapter “26.2.22.5”, page 151.

In addition to the monitor there is an end position slave pointer. This indicates the minimum and maximum position
of the determined end positions. The slave pointer can be reset by pressing the

CLEAR

key.

Display.STROKE.CHECK

Description.of.the.functions

EXIT

29-9-1

STROKE.CHECK

MAX

MIN

LIMIT

HISTORY

30. 9 %

67.6.%

MAX indicates the maximum position of the slave pointer
MIN indicates the minimum position of the slave pointer
The tolerance band for the physical end positions can be set in the

LIMIT

submenu. A message is output if the temperature goes outside the per-
mitted range.

Example:
Input upper end position

TOL MAX = 1 %

If the position is less than -1 %, a message is output

Input lower end position

TOL ZERO = 1 %

If the position is greater than 101 %, a message is output

The history entries of the last 3 messages can be viewed and deleted in
the

HISTORY submenu.

Table 90:

STROKE.CHECK; end position monitor

english

Type 8792, 8793

This manual is related to the following products: