83
Start-Up
25.
BASIC SETTING OF THE PROCESS
CONTROLLER
25.1.
P.CONTROL – Setting up and parameterization of
the process controller
To start up the process controller, you must make the following settings in the
P.CONTROL menu:
1.
SETUP
Set up the process controller (configuration)
2.
PID.PARAMETER
Parameterize process controller
Operating structure:
EXIT
EXIT
PID.PARAMETER
SETUP
DBND 0.1 %
PV-INPUT
KP 0.00
PV SCALE
TN 0.5
SP-INPUT
TV 0.0
SP-SCALE*
X0 0.0 %
P.CO-INIT
FILTER 0
P.CONTROL
ENTER
ENTER
ENTER
EXIT
*
The SP SCALE function is indicated only if the external set-point value default (external) menu option is activated under
SP INPUT.
Figure 35:
Operating structure P.CONTROL
Key:.
①
Insensitivity range (dead band) of the PID process controller
②
..Amplification factor of the process controller
③
..Reset time
④
..Hold-back time
⑤
..Operating point
⑥
..Filtering of the process actual value input
⑦
..Indication of the signal type for process actual value (4 - 20 mA, frequency input, Pt 100 input)
⑧
..Specification of the physical unit and scaling of the process actual value
⑨
..Type of set-point value default (internal or external)
⑩
..Scaling of the process set-point value (only for external set-point value default)
⑪
..Enables a smooth switchover between AUTOMATIC and MANUAL mode
English
Type 8792, 8793