beautypg.com

Burkert Type 8793 User Manual

Page 126

background image

126

Auxiliary functions

SafePos.–.Approaching.a.safety.position:
The behavior of the actuator depends on the activation of the

SAFEPOS auxiliary function.

See Chapter “26.2.11. SAFEPOS – Input the safety position”.
SAFEPOS activated:

The actuator moves to the safety position which is specified in the

SAFEPOS auxiliary

function.

SAFEPOS deactivated: The actuator moves to the safety end position which it would assume if the electrical

and pneumatic auxiliary power failed.
See Chapter “11.8. Safety end positions after failure of the electrical or pneumatic
auxiliary power”
.

Binary input = 1

→ Actuator moves to the set safety position.

Manu/Auto.–.Switching.between.the.MANUAL.and.AUTOMATIC.operating.states:

Binary input = 0

→ Operating state AUTOMATIC

AUTO

Binary input = 1

→ Operating state MANUAL

MANU

If the

Manu/Auto function was selected in the BINARY.IN menu, it is no longer possible to change the

operating state on the process level using the keys

MANU

and

AUTO

.

X.TUNE.–.Starting.the.function.X.TUNE:
Binary input = 1

→ Starting X.TUNE

X.CO/P.CO.–.Switching.between.position.and.process.controller:
This menu option stands only for Type 8793 and is available when process controller (

P.CONTROL) has been

activated.
Binary input = 0

→ Position controller (X.CO)

Binäreingang = 1

→ Process controller (P.CO)

english

Type 8792, 8793

This manual is related to the following products: