Operating voltage, Output signals to the control centre (e.g. plc) – Burkert Type 8793 User Manual
Page 58
58
Installation
Type 8792, 8793
english
15.2.2. Output signals to the control centre (e.g. PLC)
(required for analogue output and/or binary output option
only)
→
Connect terminals according to the model (options) of the positioner.
Terminal Configuration
On.the.device.side
External.circuit./.Signal.level
83 +
Binary output 1
83 +
24 V / 0 V, NC / NO specific to
operating voltage GND (terminal GND)
85 +
Binary output 2
85 +
24 V / 0 V, NC / NO specific to
operating voltage GND (terminal GND)
31 +
Analogue feedback +
31 +
+ (0/4 – 20 mA or 0 – 5 / 10 V)
completely galvanically isolated
32 –
Analogue feedback GND
32 –
GND Analogue feedback
Table 17:
Terminal assignment; output signals to the control centre
15.2.3. Operating voltage
Terminal Configuration
On.the.device.side
External.circuit./.Signal.level
+24 V
Operating voltage +
+24 V
GND
24 V DC ± 10%
max. residual ripple 10%
GND
Operating voltage GND
Table 18:
Terminal configuration; operating voltage
15.2.4. Terminal assignment for external position sensor
(for remote model only)
Connection of the digital, contact-free position sensor Type 8798:
Terminal
Wire.colour
Configuration
On.the.device.
side
External.circuit./.Signal.
level
Cable.type.
1
Cable.type.
2
S +
brown
brown
Supply sensor +
S +
+
Remote
Sensor
Type 8798
digital
S -
white
black
Supply sensor –
S –
–
A
green
red
Serial interface, A-line
A
A-line
B
yellow
orange
Serial interface, B-line
B
B-line
Table 19:
Terminal assignment; digital, contact-free position sensor Type 8798