beautypg.com

Operating voltage, Output signals to the control centre (e.g. plc) – Burkert Type 8793 User Manual

Page 58

background image

58

Installation

Type 8792, 8793

english

15.2.2. Output signals to the control centre (e.g. PLC)

(required for analogue output and/or binary output option
only)

Connect terminals according to the model (options) of the positioner.

Terminal Configuration

On.the.device.side

External.circuit./.Signal.level

83 +

Binary output 1

83 +

24 V / 0 V, NC / NO specific to
operating voltage GND (terminal GND)

85 +

Binary output 2

85 +

24 V / 0 V, NC / NO specific to
operating voltage GND (terminal GND)

31 +

Analogue feedback +

31 +

+ (0/4 – 20 mA or 0 – 5 / 10 V)
completely galvanically isolated

32 –

Analogue feedback GND

32 –

GND Analogue feedback

Table 17:

Terminal assignment; output signals to the control centre

15.2.3. Operating voltage

Terminal Configuration

On.the.device.side

External.circuit./.Signal.level

+24 V

Operating voltage +

+24 V

GND

24 V DC ± 10%
max. residual ripple 10%

GND

Operating voltage GND

Table 18:

Terminal configuration; operating voltage

15.2.4. Terminal assignment for external position sensor

(for remote model only)

Connection of the digital, contact-free position sensor Type 8798:

Terminal

Wire.colour

Configuration

On.the.device.
side

External.circuit./.Signal.
level

Cable.type.
1

Cable.type.
2

S +

brown

brown

Supply sensor +

S +

+

Remote

Sensor

Type 8798

digital

S -

white

black

Supply sensor –

S –

A

green

red

Serial interface, A-line

A

A-line

B

yellow

orange

Serial interface, B-line

B

B-line

Table 19:

Terminal assignment; digital, contact-free position sensor Type 8798

This manual is related to the following products: