32.7. Terminating circuit for DeviceNet systems

When installing a DeviceNet system, ensure that the terminating circuit of the data lines is correct. The circuit prevents
the occurrence of interference caused by signals reflected onto the data lines. The trunk line must be terminated at
both ends with resistors of 120 Ω each and 1/4 W power loss (see “Figure 127: Network topology, DeviceNet”).

32.8. Network topology of a DeviceNet system

Line with one trunk line and several drop lines.

Trunk and drop lines are made of identical material (see “Figure 127: Network topology, DeviceNet”).

Trunk line
DeviceNet cable

Terminating
resistor
120 Ω
¼ W

Terminating
resistor
120 Ω
¼ W

Drop lines
DeviceNet cable,
max. 6 m long

T01

Tn

Subscriber 1 (node 1)

Subscriber n (node n)

V + *
V –*

CAN_H

CAN_L

* not assigned, as separate power supply

Figure 127: Network topology, DeviceNet