89
Start-Up
Key
Action
Description
3..Setting.K-factor.(only.available.for.frequency.signal.type).
/
Select
K-factor
ENTER
Press
The submenu for the setting of the K-factor is displayed.
either
/
Select
VALUE
Manual.input.of.the.K-factor..
INPUT
Press
The input screen is opened. The decimal point has a dark
background.
Select decimal point
Specify position of the decimal point.
<–
Select value
The last digit of the value has a dark background.
/
<–
Select decimal place
Increase value
Set K-factor.
OK
Press
Return to
K-factor.
or
/
Select
TEACH-IN
Calculating.the.K-factor.by.measuring.a.specific.flow.rate.
ENTER
Press
for approx. 5 s
The valve is being closed.
START
Press
The container is being filled.
STOP
Press
The measured volume is displayed and the input screen is opened.
The decimal point has a dark background.
Select decimal point
Specify position of the decimal point.
<–
Select value
The last digit of the value has a dark background.
/
<–
Select decimal place
Increase value
Set the measured volume.
OK
Press
Return to
TEACH-IN.
EXIT
Press
Return to
K-factor.
EXIT
Press
Return to
PV-SCALE.
EXIT
Press
Return to
SETUP.
Table 40:
PV-SCALE; scaling process actual value
If the submenu is left by pressing the left selection key
ESC
, the value remains unchanged.