Set.factory – resetting to the factory settings – Burkert Type 8793 User Manual
Page 138
138
Auxiliary functions
26.2.16.
SET.FACTORY – Resetting to the factory settings
This function allows all settings implemented by the user to be reset to the delivery status.
All EEPROM parameters with the exception of the calibration values are reset to default values. Then a hardware
reset is implemented.
Hold down as long as countdown
(5 ...) is running
RUN
SET.FACTORY
factory
reset
Figure 78:
Operating structure SET.FACTORY
Resetting.to.the.factory.settings:
Key
Action
Description
MENU
Press
for approx. 3 s
Switching from process level
setting level.
/
Select
SET.FACTORY
(To do this, the auxiliary function must be incorporated into the main
menu).
RUN
Press
for approx. 3 s
(until progress bar is closed)
"factory reset" is shown.
Reset is implemented.
EXIT
Press
Switching from setting level
process level.
Table 67:
SET.FACTORY; Resetting to the factory settings
To adjust the Type 8792/8793 to the operating parameters, re-implement self-parameterization of the
positioner (
X.TUNE).
english
Type 8792, 8793