Start-Up

Possible.error.messages.when.running P.TUNE:

Display

Cause of fault

Remedial action

TUNE
err/break

Manual termination of self-optimization by
pressing the

EXIT

key.

P.TUNE
ERROR 1

No supply pressure connected.

Connect supply pressure.

No change to process variable.

Check process and, if required, switch on
pump or open the shut-off valve.

Check process sensor.

Table 51:

P.TUNE; possible error messages

After making all the settings described in Chapter "Start-Up", the process controller is ready for use.

Activation and configuration of auxiliary functions is described in the following Chapter "26. Configuring the aux-
iliary functions"
.