beautypg.com

X.time – limiting the control speed – Burkert Type 8793 User Manual

Page 118

background image

118

Auxiliary functions

26.2.7.

X.TIME – Limiting the control speed

Use this auxiliary function to specify the opening and closing times for the entire stroke and limit the control speeds.

When the

X.TUNE function is running, the minimum opening and closing time for the entire stroke is auto-

matically entered for

Open and Close. Therefore, movement can be at maximum speed.

Factory setting: values determined at the factory by the

X.TUNE

If the control speed is limited, values can be input for Open and Close which are between the minimum values
determined by the X.TUNE and 60 s.

EXIT

*

OK

Enter
value

Enter
value

X.TIME

Open 1

Close 1

Opening time for entire stroke
(in seconds)
Adjustment range: 1 – 60 seconds

Closing time for entire stroke
(in seconds)
Adjustment range: 1 – 60 seconds

ENTER

INPUT

INPUT

* If the submenu is left by pressing the

ESC

key, the value remains unchanged.

Figure 66:

Operating structure X.TIME

The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key

EXIT

. During the save process, the save

symbol is indicated on the display.

Effect.of.limiting.the.opening.speed.when.there.is.a.jump.in.the.set-point.value

Set-point

value

Actual value

Open

t

Valve stroke [%]

(

POS, CMD)

Figure 67:

Graph - X.TIME

english

Type 8792, 8793

This manual is related to the following products: