beautypg.com

Pos.sensor – setting interface remote path sensor, Service – Burkert Type 8793 User Manual

Page 142

background image

142

Auxiliary functions

26.2.19.

POS.SENSOR – Setting interface remote path sensor

The interface for the connection of an external path sensor can be selected in this menu.

The

POS.SENSOR menu option is available for Type 8793 Remote only.

The following connection options are possible:

Interface

sensor

Setting.in.the.menu.(ADD.FUNCTION)

digital (serial)

Remote sensor Type 8798.

POS.SENSOR DIGITAL

analog (4 - 20 mA) *

Any, high-resolution path sensor. POS.SENSOR ANALOG

Table 69:

Connection options type 8793 with external position sensor

* If the path sensor is connected to the process controller type 8793 via the analog interface, it can be

operated only as a positioner (position controller).

The

P.CONTROL auxiliary function is automatically removed.

POS.SENSOR

DIGITAL

EXIT

ENTER

ENTER

The position signal of the path sensor is
transmitted digitally

ANALOG

The position signal of the path sensor is
transmitted in analog mode

Figure 81:

Operating structure POS.SENSOR

Digital interface (menu option

POS.SENSOR

DIGITAL):

Type 8792/8793 is connected to the path sensor Type 8798 via a digital interface
(see Chapter “Terminal assignment for external position sensor (for remote model only)”, page 58).

Analog interface (menu option

POS.SENSOR

ANALOG):

Type 8793 is connected via a 4 ... 20 mA interface to any path sensor with 4 ... 20 mA output signal. To do
this, the path sensor is connected to the process actual value input (see Chapter “Terminal assignments of the
process actual value input”, page 59).

If the path sensor requires an additional power supply of 24 V DC, it can be supplied via the positioner.

26.2.20.

SERVICE

This function is of no importance to the operator of Type 8792/8793. It is for internal use only.

english

Type 8792, 8793

This manual is related to the following products: