Error messages on field bus devices – Burkert Type 8793 User Manual

Page 233

background image

233

Maintenance and Troubleshooting

35.1.5. Error Messages on Field Bus Devices

Display

Causes.of.error

Remedial.action

MFI fault

Field bus board defective.

Not possible, device defective.

Table 127:

Error Messages on Field Bus Devices

On.DeviceNet:

Display
(is displayed
approx. every
3 seconds)

Device.status

Explanation

Troubleshooting

BUS offline

Offline

Device is not connected to the bus.

The network access procedure
(Duplicate MAC-ID-Test, duration
approx. 2 s) has still not ended.

The device is the only active network
node.

• Check whether the baud rate has

been correctly set network-wide.

• Bus connection including plug

assignment correct.

• Check operating supply and bus

connection of the other nodes.

BUS no
connection

Online,

no connection
to the master

Device is connected correctly to the
bus, the network access procedure
has ended without errors, however
there is no established connection
to the master.

• New connection established by

master.

BUS timeout

I/O connection
timeout

An I/O connection is in the TIME
OUT state.

• New connection established by

master.

• Ensure that I/O data is transferred

cyclically or, if COS confirmed, that
corresponding Acknowledge mes-
sages are sent by the master.

BUS critical err

Critical bus
error

Other device with the same
address in the network.

BUS offline due to communication
problems.

• Change address of the device and

restart device

• Error analysis in the network with a

bus monitor.

Table 128:

Error message DeviceNet

On.PROFIBUS:

Display

Device.status Explanation

Troubleshooting

BUS offline

is displayed approx.
every 3 seconds

Offline.

Device is not connected to the
bus.

• Check bus connection including

plug assignment

.

• Check operating voltage and bus

connection of the other nodes.

Table 129:

Error message PROFIBUS

english

Type 8792, 8793