Bus.comm – settings on type 8792/8793, Bus.comm – settings.on.type.8792/8793 – Burkert Type 8793 User Manual
Page 218
218
DeviceNet
33.3.
BUS.COMM – Settings on Type 8792/8793
Set the following menu options in the
BUS.COMM menu for start-up of the DeviceNet version:
Address 0
Enter.a.device.address.(value between 0 and 63)
BAUD RATE
Selection.of.the.baud.rate
• The baud rate can be changed either by pressing the operator keys on the device or via the bus.
• A change has no effect until a reset (send a reset message to the identity object) or power up is implemented.
This means if the changed baud rate attribute is accessed before a reset or power up, the read (changed)
value does not agree with the still current baud rate (to be changed) of the network.
Select 125 kbit/s, 250 kbit/s or 500 kbit/s
BUS FAIL
Activate.or.deactivate.approach.of.the.safety.position
Selection SafePos off – The actuator remains in the position which corresponds to the set-point value last
transferred (default setting).
Selection SafePos on –..If there is a fault in the bus communication, the behavior of the actuator depends on
the activation of the
SAFEPOS auxiliary function.
See Chapter “26.2.11. SAFEPOS – Input the safety position”.
SAFEPOS activated:
The actuator moves to the safety position which is specified in the
SAFEPOS aux-
iliary function.
SAFEPOS deactivated:
The actuator moves to the safety end position which it would assume if the elec-
trical and pneumatic auxiliary power failed. See Chapter “11.8. Safety end positions
after failure of the electrical or pneumatic auxiliary power”.
Procedure:
Key
Action
Description
MENU
Press
for approx. 3 s
Switching from process level
setting level.
/
Select
BUS.COMM
Selection in the main menu (MAIN).
ENTER
Press
The submenu options for basic settings can now be selected.
Setting.device.address
/
Select
Address
INPUT
Press
The input screen is opened.
/
Increase value
Reduce value
Enter a device address (value between 0 and 63).
OK
Press
Return to
BUS.COMM.
english
Type 8792, 8793