208

DeviceNet

Drop line length

(Drop Lines)

Baud.rate

Length.of.the.drop.lines

Maximum.length

Maximum.total.length.Drop.lines.
in.the.network

125 kbaud

6 m for all baud rates

156 m

250 kbaud

78 m

500 kbaud

39 m

Table 110:

DeviceNet; drop line length

31.3. interfaces

Input for process
actual value*
4 – 20 mA
frequency
Pt 100

Binary input

24 V DC

Type.8792/8793

DeviceNet

2 binary outputs

24 V PNP

Initiator 1 / Initiator 2

24 V PNP NO

Inputs

Outputs

Supply

Operation

Note:
Optional inputs and outputs are illustrated by dotted lines

Bus

Bus

*

only for process controller Type 8793

Figure 124: DeviceNet interfaces

31.4. Safety settings if the bus fails

The position is approached which corresponds to the set-point value last transferred (default setting).

Other setting options (see chapter “33.3. BUS.COMM – Settings on Type 8792/8793”

).