Auxiliary functions

26.2.15.1. Calibration of the position actual value and the position set-

point value

Key

Action

Description

MENU

Press

for approx. 3 s

Switching from process level

setting level.

/

Select

CAL.USER

(To do this, the auxiliary function must be incorporated into the main
menu).

ENTER

The submenu options are displayed.

calibr. POS - Calibration of the position actual value (0 - 100 %):

/

Select

calibr.POS

ENTER

Press

The menu options for the minimum and the maximum position actual
values are displayed.

/

Select

POS. pMin

INPUT

Press

The input screen for the lower value (

POS.lower) is opened.

/

OPN

Open more

CLS

Close more

Approach minimum position of the valve.

OK

Press

Transfer and simultaneous return to the

calibr.POS menu.

/

Select

POS. pMax

INPUT

Press

The input screen for the upper value (

POS.upper) is opened.

/

OPN

Open more

CLS

Close more

Approach maximum position of the valve.

OK

Press

Transfer and simultaneous return to the

calibr.POS menu.

EXIT

Press

Acknowledgment and simultaneous return to the

CAL.USER menu.

calibr. INP calibration of the position set-point value (4 ... 20 mA; 0 ... 20 mA; 0 ... 5 V, 0 ... 10 V):

/

Select

calibr.INP

ENTER

Press

The menu options for the minimum and maximum value of the input
signal are displayed.

/

Select

INP 0mA (4mA/0V)

The minimum value for the input signal is displayed.

-

-

Apply the minimum value to the input.

OK

Press

Transfer and simultaneous return to the

calibr.INP menu.

/

Select

INP 20mA (5V/10V)

The maximum value for the input signal is displayed.

-

-

Apply the maximum value to the input.

OK

Press

Transfer and simultaneous return to the

calibr.INP menu.

EXIT

Press

Acknowledgment and simultaneous return to the

CAL.USER menu.

EXIT

Press

Acknowledgment and simultaneous return to the main menu (MAIN).

EXIT

Press

Switching from setting level

process level.

Table 64:

CAL.USER; calibration of position actual value and position set-point value