Burkert Type 8793 User Manual
Page 135
135
Auxiliary functions
26.2.15.1. Calibration of the position actual value and the position set-
point value
Key
Action
Description
MENU
Press
for approx. 3 s
Switching from process level
setting level.
/
Select
CAL.USER
(To do this, the auxiliary function must be incorporated into the main
menu).
ENTER
The submenu options are displayed.
calibr. POS - Calibration of the position actual value (0 - 100 %):
/
Select
calibr.POS
ENTER
Press
The menu options for the minimum and the maximum position actual
values are displayed.
/
Select
POS. pMin
INPUT
Press
The input screen for the lower value (
POS.lower) is opened.
/
OPN
Open more
CLS
Close more
Approach minimum position of the valve.
OK
Press
Transfer and simultaneous return to the
calibr.POS menu.
/
Select
POS. pMax
INPUT
Press
The input screen for the upper value (
POS.upper) is opened.
/
OPN
Open more
CLS
Close more
Approach maximum position of the valve.
OK
Press
Transfer and simultaneous return to the
calibr.POS menu.
EXIT
Press
Acknowledgment and simultaneous return to the
CAL.USER menu.
calibr. INP calibration of the position set-point value (4 ... 20 mA; 0 ... 20 mA; 0 ... 5 V, 0 ... 10 V):
/
Select
calibr.INP
ENTER
Press
The menu options for the minimum and maximum value of the input
signal are displayed.
/
Select
INP 0mA (4mA/0V)
The minimum value for the input signal is displayed.
-
-
Apply the minimum value to the input.
OK
Press
Transfer and simultaneous return to the
calibr.INP menu.
/
Select
INP 20mA (5V/10V)
The maximum value for the input signal is displayed.
-
-
Apply the maximum value to the input.
OK
Press
Transfer and simultaneous return to the
calibr.INP menu.
EXIT
Press
Acknowledgment and simultaneous return to the
CAL.USER menu.
EXIT
Press
Acknowledgment and simultaneous return to the main menu (MAIN).
EXIT
Press
Switching from setting level
process level.
Table 64:
CAL.USER; calibration of position actual value and position set-point value
english
Type 8792, 8793