beautypg.com

X.limit – limits the mechanical stroke range – Burkert Type 8793 User Manual

Page 117

background image

117

Auxiliary functions

26.2.6.

X.LIMIT – Limits the mechanical stroke range

This auxiliary function limits the (physical) stroke to specified % values (minimum and maximum). In doing so, the
stroke range of the limited stroke is set equal to 100 %.

If the limited stroke range is left during operation, negative

POS values or POS values greater than 100 % are indicated.

Factory setting:

Min = 0 %,

Max = 100 %

EXIT

*

OK

Enter
value

Enter
value

X.LIMIT

Min 0 %

Max 100 %

Input the initial value of the stroke
range as %.
Adjustment range:
0 – 50 % of the total stroke

Input the final value of the stroke
range as %.
Adjustment range:
50 – 100 % of the total stroke

ENTER

INPUT

INPUT

The minimum gap between Min

and Max

is 50 %

* If the submenu is left by pressing the

ESC

key, the value remains unchanged.

Figure 64:

Operating structure X.LIMIT

The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key

EXIT

. During the save process, the save

symbol is indicated on the display.

Limited stroke

Unlimited stroke

Physical stroke (%)
(

POS)

Limited stroke (%)
(

POS)

Set-point value [mA]
(

INPUT)

Adjustment range in MANUAL mode

Control range in

AUT

OMA

TIC

operating state

Figure 65:

Graph - X.LIMIT

english

Type 8792, 8793

This manual is related to the following products: