Burkert Type 8793 User Manual
Page 60
60
Installation
Type 8792, 8793
english
Input.type*
Terminal Configuration
On.the.device.side External.circuit
Frequency
- externally
supplied
actual value
1
not used
2
Clock input +
2
Clock +
3
not used
4
Clock input –
4
Clock –
Pt 100
(see infor-
mation
below)
actual value
1
not used
2
3
4
Pt 100
2
Process actual 1 (Power supply)
3
Process actual 3 (GND)
4
Process actual 2 (Compensation)
*
Can be adjusted via software (see chapter“21. Start-up sequence”).
Table 21:
Terminal assignments of the process actual value input
Connect the Pt 100 sensor via 3 cables for cable compensation reasons.
It is essential to bridge Pin 3 and Pin 4 on the sensor.
When the operating voltage is applied, the process controller is operating.
→
Now make the required basic settings and actuate the automatic adjustment of the process controller. The
procedure is described in chapter “21. Start-up sequence”.