Installation

Type 8792, 8793

english

Input.type*

Terminal Configuration

On.the.device.side External.circuit

Frequency
- externally
supplied

actual value

1

not used

2

Clock input +

2

Clock +

3

not used

4

Clock input –

4

Clock –

Pt 100
(see infor-
mation
below)

actual value

1

not used

2

3
4

Pt 100

2

Process actual 1 (Power supply)

3

Process actual 3 (GND)

4

Process actual 2 (Compensation)

*

Can be adjusted via software (see chapter“21. Start-up sequence”).

Table 21:

Terminal assignments of the process actual value input

Connect the Pt 100 sensor via 3 cables for cable compensation reasons.
It is essential to bridge Pin 3 and Pin 4 on the sensor.

When the operating voltage is applied, the process controller is operating.

Now make the required basic settings and actuate the automatic adjustment of the process controller. The
procedure is described in chapter “21. Start-up sequence”.