Connecting the process controller type 8793, . connecting.the.process.controller.type.8793, X5 - m8, 4-pole circular connector – Burkert Type 8793 User Manual
Page 55: Plug assignments of the process actual value input
55
Installation
Type 8792, 8793
english
14.4. Connecting the process controller Type 8793
→
First connect the process controller as described in chapter “14.2. Connection of the positioner Type 8792”.
14.4.1. X5 - M8, 4-pole circular connector,
plug assignments of the process actual value input
Input.type* Pin
Wire.
colour**
Configuration
DIP.
switches
On.the.
device.side
External.circuit
4 – 20 mA-
internally
supplied
1
brown
+24 V transmitter supply
Switch
on left
1
2
3
4
Transmitter
GND
2
white
Output from transmitter
3
blue
GND (identical with GND
operating voltage)
4
black
Bridge to GND (Pin 3)
4 – 20 mA-
externally
supplied
1
brown
not used
Switch
on right
2
white
Process actual +
2
4 - 20 mA
3
blue
not used
4
black
Process actual –
4
GND 4 - 20 mA
Frequency-
internally
supplied
1
brown
+24 V sensor supply
Switch
on left
1
+24 V
2
white
Clock input +
2
Clock +
3
blue
Clock input – (GND)
3
Clock – / GND
(identical with GND
operating voltage)
4
black
not used
Frequency-
externally
supplied
1
brown
not used
Switch
on right
2
white
Clock input +
2
Clock +
3
blue
Clock input –
3
Clock –
4
black
not used
Pt 100
(see infor-
mation
below)
1
brown
not used
Switch
on right
2
3
4
Pt 100
2
white
Process actual 1 (power supply)
3
blue
Process actual 3 (GND)
4
black
Process actual 2 (compensation)
*
Can be adjusted via software (see chapter “21. Start-up sequence”).
**
The indicated colors refer to the connection cable available as an accessory (918718).
Table 15:
Pin assignment; X5 - M8, 4-pole circular connector - process actual value input
Connect the Pt 100 sensor via 3 cables for cable compensation reasons. It is essential to bridge Pin 3
and Pin 4 on the sensor.
When the operating voltage is applied, the process controller is operating.
→
Now make the required basic settings and actuate the automatic adjustment of the process controller. The
procedure is described in chapter “21. Start-up sequence”.