Start-Up
Operating structure:
X.TUNE
INPUT
Press for approx. 3 s
Hold.down
as long as
countdown
(5 ...) is
running
X.TUNE
STARTED
TUNE #0
INIT
X.TUNE
READY
Process.level (values are displayed)
Automatic
self-parameterization
MENU
Setting.level
RUN
EXIT
ADD.FUNCTION
EXIT
Figure 34:
Operating structure X.TUNE
Automatically.determining.dead.band.DBND.by.running.X.TUNE:
When
X.TUNE is running, the dead band can be automatically determined depending on the friction
behavior of the actuating drive.
Before running
X.TUNE, the X.CONTROL auxiliary function must be activated by incorporating it into the
main menu (MAIN).
If
X.CONTROL is not activated, a fixed dead band of 1 % is used.
The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key
EXIT
. During the save process, the save
symbol is indicated on the display.
Possible.error.messages.when.running X.TUNE:
Display
Causes.of.error
Remedial.action
TUNE
err/break
Manual termination of self-parameterization
by pressing the
EXIT
key
X.TUNE locked
The
X.TUNE function is blocked
Input access code
X.TUNE
ERROR 1
No compressed air connected
Connect compressed air
X.TUNE
ERROR 2
Compressed air failed during Autotune
(
X.TUNE).
Check compressed air supply
X.TUNE
ERROR 3
Actuator or control system deaeration side
leaking
Not possible, device defective