Burkert Type 8793 User Manual
Page 166
166
Auxiliary functions
Operating structure:
ENTER
INPUT
INPUT
ENTER
OK
OK
ESC
ESC
EXIT
CLEAR
Input
tolerance band
Input
compensation
time
History entry
is displayed
POS.MONITOR
HISTORY
Delete.history.entry
EXIT
DEADBAND
COMP.TIME
Figure 99:
Operating structure POS.MONITOR
Inputting.tolerance.band.and.compensation.time
Key
Action
Description
/
Select
POS.MONITOR
(To do this, the
POS.MONITOR function must be incorporated into
the
DIAGNOSE main menu. See Chapter “26.2.22.4. Activation of
ENTER
Press
The menu is displayed.
DEADBAND has already been selected.
INPUT
Press
The preset value is displayed.
/
Increase value
<
Changing the decimal
place
Input tolerance band.
OK
Press
Acknowledge value.
/
Select
COMP.TIME
INPUT
Press
The preset value is displayed.
/
Increase value
<
Changing the decimal
place
Input compensation time.
OK
Press
Return to the
POS.MONITOR menu.
EXIT
Press
Return to the
DIAGNOSE main menu.
Table 93:
POS.MONITOR; specifying tolerance band and compensation time.
PV.MONITOR –.Process.monitor.(for.Type.8793.only)
The
PV.MONITOR function monitors the process actual value.
The operating menu is identical to the position monitor
POS.MONITOR described above.
In contrast, it is not the position of the actuator which is monitored here but the process.
english
Type 8792, 8793