beautypg.com

Burkert Type 8793 User Manual

Page 215

background image

215

DeviceNet

32.6. X5 - M8, 4-pole circular connector - process actual

value (Type 8793 only)

Input.type* Pin

Wire.
colour.**

Configuration

DIP.
switches***

On.the.
device.side

External.circuit

4 – 20 mA
- internally
supplied

1

brown

+24 V transmitter supply

Switch on
left

1
2

3
4

Transmitter

GND

2

white

Output from transmitter

3

blue

GND (identical with the GND
operating voltage)

4

black

Bridge after GND (Pin 3)

4 – 20 mA
- externally
supplied

1

brown

not used

Switch on
right

2

white

Process actual +

2

4 – 20 mA

3

blue

not used

4

black

Process actual –

4

GND 4 – 20 mA

Frequency
- internally
supplied

1

brown

+24 V sensor supply

Switch on
left

1

+24 V

2

white

Clock input +

2

Clock +

3

blue

Clock input – (GND)

3

Clock – / GND
(identical with
the GND oper-
ating voltage)

4

black

not used

Frequency
- externally
supplied

1

brown

not used

Switch on
right

2

white

Clock input +

2

Clock +

3

blue

Clock input –

3

Clock –

4

black

not used

Pt 100
(see infor-
mation
below)

1

brown

not used

Switch on
right

2

3
4

Pt 100

2

white

Process actual 1 (power supply)

3

blue

Process actual 3 (GND)

4

black

Process actual 2 (compensation)

* Can be adjusted via software (see chapter “23.1. INPUT - Setting the input signal”).

** The indicated colors refer to the connection cable available as an accessory (918 718).

*** The switch is inside the device on the PCB (see “Figure 26: Location of the DIP switch; symbols for switch position”).

Table 116:

Plug assignments; X5 - M8, 4-pole circular connector - process actual value input; DeviceNet

Connect the Pt 100 sensor via 3 cables for cable compensation reasons. It is essential to bridge Pin 3
and Pin 4 on the sensor.

english

Type 8792, 8793

This manual is related to the following products: