Auxiliary functions
Key
Action
Description
OK
Press
Acknowledge value.
EXIT
Press
Return to the
STROKE.CHECK menu.
EXIT
Press
Return to the
DIAGNOSE main menu.
Table 91:
STROKE.CHECK; end position monitor.
POS.MONITOR –Position.monitoring
The
POS.MONITOR function monitors the current position of the actuator.
The tolerance band for the set-point value is specified in the
DEADBAND submenu.
A period for alignment of the actual value with the set-point value is specified in the
COMP.TIME submenu
(compensation time).
The compensation time
COMP.TIME starts recording as soon as the set-point value is constant. When the com-
pensation time has elapsed, monitoring starts.
If the control deviation (DEV) of the actual value is greater than the tolerance band of the set-point value during
monitoring, a message is output.
• To do this, a history entry is made in the
HISTORY submenu. For description see “26.2.22.7. History entries in
• The status signal, which is assigned to the message, is indicated at short intervals on the display.
See also
D.MSG and CONFIG.MSG in Chapter “26.2.22.5”, page 151.
Display.POS.MONITOR
Description.of.the.functions
EXIT
INPUT
29-11-1
POS:MONITOR
DEADBAND
HISTORY
COMP.TIME
10.0 sec
2.0.%
The tolerance band of the set-point value preset at the factory to 2 % can
be changed in the
DEADBAND submenu.
The compensation time is set in
COMP.TIME (compensation time).
The history entries of the last 3 messages can be viewed and deleted in
the
HISTORY submenu.
Table 92:
POS.MONITOR; position monitor
Schematic representation
0
0.2
0.4
0.6
0.8
1
1.2
1.4
0
1
2
3
4
5
6
7
8
9
10
COMP.TIME
DEADBAND
CMD
POS
DEV
Key:
DEADBAND = adjustable tolerance
band as %.
COMP.TIME = adjustable time
in seconds expected until the
control deviation is compared with
the tolerance band.
DEV = control deviation
Figure 98:
POS.MONITOR; schematic representation of position monitor
english
Type 8792, 8793