beautypg.com

Configuration via the control (profibus dp master), Configuration of the process values – Burkert Type 8793 User Manual

Page 200

background image

200

PROFIBUS DP

30.4. Configuration via the control (PROFIBUS DP

Master)

The configuration requires the following components:

• Software suitable for the configuration. For example Step7 from Siemens A brief description of this can be

found in the following chapter “30.5. Configuration with Siemens Step7”.

• GSD file (download from the Bürkert homepage:)

30.4.1. Supplementary literature on the configuration of the

PROFIBUS DP

More detailed information can be found in the supplementary instructions on the Bürkert homepage:

• „Configuration on the PROFIBUS by means of GSD file“

www.burkert.com → Type 8792 or Type 8793 → Config. PROFIBUS by GSD-file

30.4.2. Configuration of the process values

The PDI (Process Data Input) input first.

PDI: Process.Data.Input (from the Type 8792/8793 to the controller)

Name

Description

Identifier

PDI:POS

Actual position (position)

Actual value of positioner as ‰. Value range 0 – 1000.
Values < 0 or > 1000 are possible if e.g. Autotune has not run
through correctly.

GSD file:

PDI:POS



Identifier (HEX): 41, 40, 00

PDI:CMD

Nominal position (command)

Set-point value of positioner as ‰. Value range 0 – 1000.

GSD file:

PDI:CMD

Identifier (HEX): 41, 40, 01

PDI:PV

PDI:SP

Process actual value (process value)

Actual value of process controller in physical unit
(as set in the menu

P.CONTROL SETUP PV-INPUT or

PV-SCALE),
max. value range -999 – 9999, depending on internal scaling

Process set-point value (setpoint)

Set-point value of process controller in physical unit
(as set in the menu

P.CONTROL SETUP SP-INPUT or

SP-SCALE),
max. value range -999 – 9999, depending on internal scaling

GSD file:

PDI:PV




Identifier (HEX): 41, 40, 02


GSD file:

PDI:SP




Identifier (HEX): 41, 40, 03

PDI:TEMP

Device temperature (temperature)

Temperature of 0.1 °C is measured on the CPU board by the
sensor,

Value range -550 (-55 °C) – +1250 (+125 °C)

GSD file:

PDI:TEMP

Identifier (HEX): 41, 40, 04

english

Type 8792, 8793

This manual is related to the following products: