136

Auxiliary functions

26.2.15.2. Calibration of the process set-point value and process actual

value

Key

Action

Description

MENU

Press

for approx. 3 s

Switching from process level

setting level.

/

Select

CAL.USER

(To do this, the auxiliary function must be incorporated into the main
menu).

ENTER

The submenu options are displayed.

calibr. SP - calibration of the process set-point value:

/

Select

calibr.SP

ENTER

Press

The menu options for the minimum and the maximum process set-
point values are displayed.

/

Select

SP 0mA (4mA/0V)

The minimum value for the input signal is displayed.

-

-

Apply the minimum value to the input.

OK

Press

Transfer and simultaneous return to the

calibr.SP menu.

/

Select

SP 20mA (5V/10V)

The maximum value for the input signal is displayed.

-

-

Apply the maximum value to the input.

OK

Press

Transfer and simultaneous return to the

calibr.SP menu.

EXIT

Press

Acknowledgment and simultaneous return to the

CAL.USER menu.

calibr. PV - calibration of the process actual value for input signal 4 - 20 mA:

/

Select

calibr.PV

ENTER

Press

The menu options for the minimum and the maximum process actual
values are displayed.

/

Select

PV 4mA

The minimum value for the input signal is displayed.

-

-

Apply the minimum value to the input.

OK

Press

Transfer and simultaneous return to the

calibr.PV menu.

/

Select

PV 20mA

The maximum value for the input signal is displayed.

-

-

Apply the maximum value to the input.

OK

Press

Transfer and simultaneous return to the

calibr.PV menu.

EXIT

Press

Acknowledgment and simultaneous return to the

CAL.USER menu.

calibr. PV - calibration of the process actual value for input signal Pt 100:

/

Select

calibr.PV

ENTER

Press

The input screen for calibration of the temperature is opened.

/

Select decimal place

Increase number

Input the current temperature.

OK

Press

Transfer and simultaneous return to the

CAL.USER menu.

EXIT

Press

Acknowledgment and simultaneous return to the main menu (MAIN).

EXIT

Press

Switching from setting level

process level.

Table 65:

CAL.USER; calibration of position actual value and position set-point value

english

Type 8792, 8793