Burkert Type 8793 User Manual
Page 136
136
Auxiliary functions
26.2.15.2. Calibration of the process set-point value and process actual
value
Key
Action
Description
MENU
Press
for approx. 3 s
Switching from process level
setting level.
/
Select
CAL.USER
(To do this, the auxiliary function must be incorporated into the main
menu).
ENTER
The submenu options are displayed.
calibr. SP - calibration of the process set-point value:
/
Select
calibr.SP
ENTER
Press
The menu options for the minimum and the maximum process set-
point values are displayed.
/
Select
SP 0mA (4mA/0V)
The minimum value for the input signal is displayed.
-
-
Apply the minimum value to the input.
OK
Press
Transfer and simultaneous return to the
calibr.SP menu.
/
Select
SP 20mA (5V/10V)
The maximum value for the input signal is displayed.
-
-
Apply the maximum value to the input.
OK
Press
Transfer and simultaneous return to the
calibr.SP menu.
EXIT
Press
Acknowledgment and simultaneous return to the
CAL.USER menu.
calibr. PV - calibration of the process actual value for input signal 4 - 20 mA:
/
Select
calibr.PV
ENTER
Press
The menu options for the minimum and the maximum process actual
values are displayed.
/
Select
PV 4mA
The minimum value for the input signal is displayed.
-
-
Apply the minimum value to the input.
OK
Press
Transfer and simultaneous return to the
calibr.PV menu.
/
Select
PV 20mA
The maximum value for the input signal is displayed.
-
-
Apply the maximum value to the input.
OK
Press
Transfer and simultaneous return to the
calibr.PV menu.
EXIT
Press
Acknowledgment and simultaneous return to the
CAL.USER menu.
calibr. PV - calibration of the process actual value for input signal Pt 100:
/
Select
calibr.PV
ENTER
Press
The input screen for calibration of the temperature is opened.
/
Select decimal place
Increase number
Input the current temperature.
OK
Press
Transfer and simultaneous return to the
CAL.USER menu.
EXIT
Press
Acknowledgment and simultaneous return to the main menu (MAIN).
EXIT
Press
Switching from setting level
process level.
Table 65:
CAL.USER; calibration of position actual value and position set-point value
english
Type 8792, 8793