Burkert Type 8793 User Manual
Page 132
132
Auxiliary functions
• OUT.type.-.Setting.the.switching.status..
In addition to selecting the output, the switching status required for the binary output must be input.
See “Table 63”.
Key
Action
Description
/
Select
OUT.type
SELEC
Press
The switching statuses
normally open and normally closed are
displayed.
/
Select switching status
SELEC
Press
The selection is marked by a filled circle .
EXIT
Press
Acknowledgment and simultaneous return to the
OUT BIN 1/2 menu.
EXIT
Press
Acknowledgment and simultaneous return to the
OUTPUT menu.
EXIT
Press
Acknowledgment and simultaneous return to the main menu (MAIN).
EXIT
Press
Switching from setting level
process level.
Table 62:
OUT.type; inputting switching status for binary output and return to the process level.
Switching.signal
Switching.statuses
normally.open
normally.closed
0
0 V
24 V
1
24 V
0 V
Table 63:
OUT BIN 1/2; switching statuses
The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key
EXIT
. During the save process, the save
symbol is indicated on the display.
english