Installation
Type 8792, 8793
english
Connection of a potentiometric position sensor:
Terminal
Configuration
On.the.device.side External.circuit
Potentiometer 1
1
Potentiometer
Center tap 2
2
Center tap
Potentiometer 3
3
Table 20:
Terminal assignment; potentiometric position sensor
When the operating voltage is applied, the positioner is operating.
→
Now make the required basic settings and actuate the automatic adjustment of the positioner. The procedure is
described in chapter “21. Start-up sequence” .
15.3. Terminal assignment for cable gland - process
controller Type 8793
→
First connect the process controller as described in chapter “15.2. Terminal assignment for cable gland -
positioner Type 8792”
15.3.1. Terminal assignments of the process actual value input
Input.type*
Terminal Configuration
On.the.device.side External.circuit
4 – 20 mA
- internally
supplied
actual value
1
+24 V transmitter input
1
2
3
GND
Transmitter
GND
2
Output from transmitter
3
Bridge to GND (Terminal GND
from operating voltage)
4
not used
GND
GND from operating voltage
4 – 20 mA
- externally
supplied
actual value
1
not used
2
Process actual +
2
+ (4 – 20 mA)
3
Process actual –
3
GND 4 – 20 mA
4
not used
Frequency
- internally
supplied
actual value
1
+24 V sensor supply
1
+24 V
2
Clock input +
2
Clock +
3
not used
4
Clock input –
4
GND
GND from operating voltage
GND
Clock – (GND)