130
Auxiliary functions
26.2.14.3. Setting of the submenu options of
OUT BIN 1 / OUT BIN 2
Key
Action
Description
MENU
Press
for approx. 3 s
Switching from process level
setting level.
/
Select
OUTPUT
(To do this, the auxiliary function must be incorporated into the main
menu).
ENTER
The outputs are displayed.
/
Select
OUT BIN1/2
ENTER
Press
Submenu options of
OUT BIN 1/2 are displayed.
Table 58:
OUT BIN1 / OUT BIN2; opening the submenu
• POS.Dev.-.Alarm.output.for.excessively.large.control.deviation.of.the.positioner
• POS.Lim-1/2 - Output.of.the.current.position.with.respect.to.a.specified.limit.position
Key
Action
Description
POS.Dev - Alarm output for excessively large control deviation of the positioner:
/
Select
POS.Dev
SELEC
Press
The input screen for the limit value
(Deviation:) is opened.
/
Increase value
Reduce value
Input limit value for permitted control deviation.
Adjustment range: 1 ... 50 % (must not be less than the dead band).
OK
Press
Acknowledgment and simultaneous return to the
OUT BIN 1/2 menu.
Then set the required switching status in the
OUT.type submenu.
POS.Lim-1/2 - Output of the current position with respect to a specified limit position:
/
Select
POS.Lim-1/2
SELEC
Press
The input screen for the limit position
(Limit:) is opened.
/
Increase value
Reduce value
Input limit position.
Adjustment range: 0 ... 100 %.
OK
Press
Acknowledgment and simultaneous return to the
OUT BIN 1/2 menu.
Then set the required switching status in the
OUT.type submenu.
Table 59:
OUT BIN1 / OUT BIN2; setting value for POS.Dev or POS.Lim-1/2
english