Start-up devicenet, Safety instructions, Start-up sequence – Burkert Type 8793 User Manual
Page 217: Start-up.devicenet, . safety.instructions, . start-up.sequence

217
DeviceNet
33.
START-UP DEVICENET
33.1. Safety instructions
WARNING!
Risk.of.injury.from.improper.operation!
Improper operation may result in injuries as well as damage to the device and the area around it
• Before start-up, ensure that the operating personnel are familiar with and completely understand the contents
of the operating instructions.
• Observe the safety instructions and intended use.
• Only adequately trained personnel may start up the equipment/the device.
Before start-up, carry out fluid installation (see Chapter “13”) and electrical installation (Chapter “32”) of
Type 8792/8793 and of the valve.
33.2. Start-up sequence
The following basic settings are required for start-up of the DeviceNet version of Type 8792/8793:
Device.type
Sequence Type.of.basic.setting
Setting.via
Description.
in.chapter
8792 and 8793
1
Adjust device to the local conditions
X.TUNE
For.8793.only
(Process
control)
2
Activate process controller.
ADD.FUNCTION “24”
8792 und 8793
Settings on Type 8792/8793:
BUS.COMM
3
Input device address.
4
Select baud rate.
5
Activate or deactivate safety position.
Configuration:
The process data is transferred via an
I/O connection.
DeviceNet Master
by means of ESD
file and special
software
5
Initialize the I/O connection to transfer the
– Static Input Assemblies
– Static Output Assemblies.
Table 117:
Start-up sequence for DeviceNet
english
Type 8792, 8793