Burkert Type 8793 User Manual
Page 201
201
PROFIBUS DP
Name
Description
Identifier
PDI:MODE
Operating state (operation mode)
Operating state:
GSD file:
PDI:MODE
0:
AUTO
1:
MANUAL
2:
XTUNE
9:
P.QLIN
10: P.TUNE
12: BUSSAFEPOS
Identifier (HEX): 41, 00, 05
PDI:ERR
Error
Indicates the number of the process value (output) which
was not written. The value is retained until it is deleted with
PDO:ERR.
HEX
14
PDO:CMD / SP
16
PDO:MODE
GSD file:
PDI:ERR
Identifier (HEX): 41, 00, 06
PDI:
PCONact
0: Positioner
1: Process controller
GSD file:
PDI:PCONact
Identifier (HEX): 41, 00, 0A
Table 107:
Process Data Input, PROFIBUS DP
PDI:PV and PDI:SP can be selected for Type 8793 (process controller) only and are beneficial only when
process controller activated.
PDI:PCONact can be selected for Type 8793 (process controller) only.
→
Then the PDO (Process Data Output) input.
PDO: Process.Data.Output (from the controller to the Type 8792/8793)
Name
Description
Identifier
PDO:CMD/
SP
for positioner Type 8792: Set-point position (input)
Set-point value of positioner as ‰. Value range 0 – 1000
If the value is too small or too large, the last valid value is used
and is indicated in
ERR with HEX 14.
GSD file:
PDO:CMD/SP
Identifier (HEX): 81, 40, 14
for process controller Type 8793: Process set-point value (setpoint)
Set-point value of process controller in physical unit
(as set in the menu
P.CONTROL → SETUP → SP-INPUT or
SP-SCALE),
max. value range -999 – 9999, depending on internal scaling.
If the value is too small or too large, the last valid value is used
and is indicated in
ERR with HEX 14.