5
2)
Preset-speed frequency setting
Set the speed (frequency) of the number of steps necessary.
Title
Funtion
Adjustment range
Default setting
UT
Preset-speed operation frequencies 1
NN
WN(Hz)
15.0
UT
Preset-speed operation frequencies 2
NN
WN(Hz)
20.0
UT
Preset-speed operation frequencies 3
NN
WN(Hz)
25.0
UT
Preset-speed operation frequencies 4
NN
WN(Hz)
30.0
UT
Preset-speed operation frequencies 5
NN
WN(Hz)
35.0
UT
Preset-speed operation frequencies 6
NN
WN(Hz)
40.0
UT
Preset-speed operation frequencies 7
NN
WN(Hz)
45.0
Examples of preset-speed contact input signals: Slide switch SW4 set to sink logic
O: ON -: OFF (Speed commands other than preset-speed commands are valid when all are OFF)
Preset-speed
Terminal
1
2
3
4
5
6
7
R-CC
{
-
{
-
{
-
{
RES-CC
-
{
{
-
-
{
{
VIA-CC
-
-
-
{
{
{
{
+
Preset-speed commands are not allocated to standard default setting. Use the input terminal function
selection to allocate SS1 to SS3 terminal.
Terminal R............... Input terminal function selection 2 (R)
H
= (Preset-speed command 1: SS1)
Terminal RES.......... Input terminal function selection 3 (RES)
H
= (Preset-speed command 2: SS2)
Terminal VIA ........... Input terminal function selection 8 (VIA)
H
= (Preset-speed command 3: SS3)
Analog/contact input function selection
H= (VIA-contact input(Sink))
[Example of a connection diagram]
(SW4 set to sink logic)
F (Forward run)
CC
P24
RES
VIA
R
Forward
Preset-speed 1 (SS1)
Preset-speed 3 (SS3)
Preset-speed 2 (SS2)
Common
VIA
V
I
SW3
CC
R
RES
VIA