beautypg.com

Selection of wiring devices – Toshiba VF-FS1 User Manual

Page 204

background image

E6581381

J-2

10

Selection of wiring devices

Input current (A)

Molded case circuit

breaker (MCCB)

Earth leakage circuit

breaker (ELCB)

Magnetic contactor

(MC)

Voltage class

Capacity of

applicable

motor

(kW)

200V class:200V
400V class:380V

200V class:240V
400V class:480V

Inverter model

Rated current (A)

Operational current(A)

AC-1

0.4

1.9

1.6

VFFS1-2004PM

3

25

0.75

3.3

2.7

VFFS1-2007PM

5

25

1.5

6.1

5.1

VFFS1-2015PM

10

25

2.2

8.7

7.3

VFFS1-2022PM

15

25

4

15.7

13.0

VFFS1-2037PM

30

25

5.5

20.8

17.3

VFFS1-2055PM

40

32

7.5

27.9

23.3

VFFS1-2075PM

50

40

11

42.1

34.4

VFFS1-2110PM

75

50

15

56.1

45.5

VFFS1-2150PM

100

80

18.5

67.3

55.8

VFFS1-2185PM

100

80

22

80.4

66.4

VFFS1-2220PM

125

100

Three-phase

200V class

30

113.3

89.5

VFFS1-2300PM

175

125

0.4

1.0

0.8

VFFS1-4004PL

3

25

0.75

1.7

1.4

VFFS1-4007PL

3

25

1.5

3.2

2.5

VFFS1-4015PL

5

25

2.2

4.6

3.6

VFFS1-4022PL

10

25

4

8.1

6.4

VFFS1-4037PL

15

25

5.5

10.9

8.6

VFFS1-4055PL

20

25

7.5

14.7

11.7

VFFS1-4075PL

30

32

11

21.1

16.8

VFFS1-4110PL

40

32

15

28.5

22.8

VFFS1-4150PL

50

40

18.5

34.8

27.8

VFFS1-4185PL

60

50

22

41.6

33.1

VFFS1-4220PL

75

80

Three-phase

400V class

Note 4)

30

56.7

44.7

VFFS1-42300PL

100

80

Note 1: Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz.
Note 2: Choose the MCCB according to the power supply capacity.

For comply with UL and CSA standard, use the fuse certified by UL and CSA.

Note 3: When using on the motor side during commercial-power supply operation, choose the MC with class

AC-3 rated current for the motor rated current.

Note 4: Attach surge killers to the magnetic contactor and exciting coil of the relay.
Note 5: In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit,

raise the reliability of the contact by using 2a-type contacts in parallel connection.