E6581381

K-9

11

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

H

0496

Waveform switching
adjustment
coefficient

kHz

0.1/0. 1

0.1-14.0

14.0

5.10

6.15.2

*1 : Default values vary depending on the capacity.

⇒ See the table of page K-14.

• Acceleration/deceleration time parameters

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

H

0500

Acceleration time
2

s

0.1/0.1

0.0-3200

* 1

H

0501

Deceleration time
2

s

0.1/0.1

0.0-3200

* 1

H

0502

Acceleration/decel
eration 1 pattern

-

-

0

H

0503

Acceleration/decel
eration 2 pattern

-

-

0: Linear
1: S-pattern 1
2: S-pattern 2

0

H

0504

Selecting an
acceleration/decel
eration pattern

-

-

1: Acceleration/deceleration 1
2: Acceleration/deceleration 2

1

H

0505

Acceleration/decel
eration 1 and 2
switching
frequency

Hz

0.1/0.01

0.0-WN

0.0

H

0506

S-pattern lower-
limit adjustment
amount

%

1/1

0-50

10

6.16

H

0507

S-pattern upper-
limit adjustment
amount

%

1/1

0-50

10

*1 : Default values vary depending on the capacity.

⇒ See the table of page K-14.

• Protection parameters

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

H

0601

Stall prevention
level 1

%

(A)

1/1

10-110,
111 (disabled)

110

6.17.2

H

0602

Inverter trip
retention selection

-

-

0: Canceled with the power off
1: Still retained with the power off

0

6.17.3

H

0603

Emergency stop
selection

-

-

0: Coast stop
1: Slowdown stop
2: Emergency DC braking

0

6.17.4

H

0604

Emergency DC
braking time

s

0.1/0.1

0.0-20.0

1.0

H

0605

Output phase
failure detection
mode selection

-

-

0: Disabled
1: At start-up (only one time after

power is turned on)

2: At start-up (each time)
3: During operation
4: At start-up + during operation
5: Detection of cutoff on output side

0

6.17.5

H

0607

Motor 150%-
overload time limit

s

1/1

10-2400

300

6.17.1

H

0608

Input phase failure
detection mode
selection

-

-

0: Disabled, 1: Enabled

1

6.17.6