beautypg.com

4 motor thermal protection, Aic, fuse and wire sizes – Toshiba VF-FS1 User Manual

Page 202

background image

E6581381

I-6

9

AIC, Fuse and Wire sizes

Voltage

class

Capacity of

applicable

motor

(kW)

Inverter model

AIC (A)

(Interrupting

capacity)

Fuse class and

current (A)

Input wire sizes of

power circuit

Out put wire sizes

of power circuit

Earth

0.4

VFFS1-2004PM

AIC 5000A

J 3A max.

AWG 14

AWG 14

AWG 14

0.75

VFFS1-2007PM

AIC 5000A

J 6A max.

AWG 14

AWG 14

AWG 14

1.5

VFFS1-2015PM

AIC 5000A

J 10A max.

AWG 14

AWG 14

AWG 14

2.2

VFFS1-2022PM

AIC 5000A

J 15A max.

AWG 14

AWG 14

AWG 14

4.0

VFFS1-2037PM

AIC 5000A

J 25A max.

AWG 12

AWG 10

AWG 12

5.5

VFFS1-2055PM

AIC 22000A

J 35A max.

AWG 10

AWG 8

AWG 10

7.5

VFFS1-2075PM

AIC 22000A

J 45A max.

AWG 8

AWG 8

AWG 10

11

VFFS1-2110PM

AIC 22000A

J 70A max.

AWG 6

AWG 6

AWG 10

15

VFFS1-2150PM

AIC 22000A

J 90A max.

AWG 4

AWG 4

AWG 10

18.5

VFFS1-2185PM

AIC 22000A

J 100 A max.

AWG 4

AWG 3

AWG 8

22

VFFS1-2220PM

AIC 22000A

J 125A max.

AWG 2

AWG 2

AWG 8

Three-phase

200V class

30

VFFS1-2300PM

AIC 22000A

J 175A max.

AWG 1/0

AWG 1/0

AWG 6

0.4

VFFS1-4004PL

AIC 5000A

J 3A max.

AWG 14

AWG 14

AWG 14

0.75

VFFS1-4007PL

AIC 5000A

J 3A max.

AWG 14

AWG 14

AWG 14

1.5

VFFS1-4015PL

AIC 5000A

J 6A max.

AWG 14

AWG 14

AWG 14

2.2

VFFS1-4022PL

AIC 5000A

J 10A max.

AWG 14

AWG 14

AWG 14

4.0

VFFS1-4037PL

AIC 5000A

J 15A max.

AWG 14

AWG 14

AWG 14

5.5

VFFS1-4055PL

AIC 22000A

J 20A max.

AWG 14

AWG 14

AWG 14

7.5

VFFS1-4075PL

AIC 22000A

J 25A max.

AWG 12

AWG 12

AWG 14

11

VFFS1-4110PL

AIC 22000A

J 35A max.

AWG 10

AWG 10

AWG 10

15

VFFS1-4150PL

AIC 22000A

J 45A max.

AWG 8

AWG 8

AWG 10

18.5

VFFS1-4185PL

AIC 22000A

J 60A max.

AWG 8

AWG 8

AWG 10

22

VFFS1-4220PL

AIC 22000A

J 70A max.

AWG 6

AWG 6

AWG 10

Three-phase

400V class

30

VFFS1-4300PL

AIC 22000A

J 90A max.

AWG 4

AWG 4

AWG 10

9.2.4 Motor thermal protection

Selects the electronic thermal protection characteristics that fit with the ratings and characteristics of the motor. In
case of multi motor operation with one inverter, thermal relay should be connected to each motor.