beautypg.com

Communication parameters – Toshiba VF-FS1 User Manual

Page 220

background image

E6581381

K-12

11

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

H

0734

Prohibition of
panel emergency
stop operation

-

-

0: Permitted
1: Prohibited

0

6.20.1

H

0735

Prohibition of
panel reset
operation

-

-

0: Permitted
1: Prohibited

0

H

0738

Head of
parameter display
selection

-

-

0: AUF
1: AUH

0

6.20.7

H

0748

Integral output
power retention
selection

-

-

0: Disabled
1: Enabled

1

6.20.8

H

0749

Display unit
selection for
integral output
power

-

-

0: 1=1kWh
1: 0.1=1kWh
2: 0.01=1kWh
3: 0.001=1kWh

*1

*1 : Default values vary depending on the capacity.

⇒ See the table of page K-14.

• Communication parameters

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

H

0800

Communication
rate

-

-

0: 9600bps
1: 19200bps

1

H

0801

Parity

-

-

0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)

1

H

0802

Inverter number

-

1/1

0-247

0

H

0803

Communication
error trip time

s

1/1

0: Disabled
1-100

0

H

0805

Communication
waiting time

s

0.01/0.01

0.00: Regular communication
0.01-2.00

0.00

H

0806

Setting of master
and slave for
communication
between inverters

-

-

0: Slave (0 Hz command issued in

case the master inverter fails)

1: Slave (Operation continued in case

the master inverter fails)

2: Slave (Emergency stop tripping in

case the master inverter fails)

3: Master (transmission of frequency

commands)

4: Master (transmission of output

frequency signals)

0

6.21

H

0811

Communication
command point 1
setting

%

1/1

0-100

0

H

0812

Communication
command point 1
frequency

Hz

0.1/0.01

0.0-200.0

0.0

H

0813

Communication
command point 2
setting

%

1/1

0-100

100

H

0814

Communication
command point 2
frequency

Hz

0.1/0.01

0.0-200.0

50.0 (WP)
60.0 (WN)

6.5.2

6.21

H

0829

Selection of
communication
protocol

-

-

0: Toshiba inverter protocol
1: ModbusRTU protocol
2: Metasys N2 protocol
3: APOGEE FLN protocol
4: BAC-net protocol

0

6.21