E6581381

F-12

6

6.3.5 Comparing the frequency command values

H

: Frequency command agreement detection range

HOQF

: Frequency setting mode selection 1

H

: Frequency setting mode selection 2

• Function

If the frequency command value specified using HOQF (or H) almost agrees with the
frequency command value from the VIA and VIB terminal with an accuracy of

± H, an ON or

OFF signal will be sent out.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Frequency command agreement detection
range

0.0

∼ HJ (Hz)

2.5

HOQF

Frequency setting mode selection 1

1

H

Frequency setting mode selection 2

1-5

2

Note: When using VIA terminal, set H or H respectively to 52 or 53 to put out signals to RY-RC or

FLA-FLB-FLC.

When using VIB terminal, set H or H respectively to 60 or 61 to put out signals to RY-RC or
FLA-FLB-FLC.

Note: This function can be used, for example, to send out a signal indicating whether the amount of

processing and the amount of feedback agree with each other when the PID function is in use.
⇒ For an explanation of the PID function, see section 6.14.