4 meter setting and adjustment – Toshiba VF-FS1 User Manual

Page 76

background image

E6581381

E-10

5

5.4

Meter setting and adjustment

HOUN

: Meter selection

HO

: Meter adjustment

• Function

The signal output from the FM terminal is an analog voltage signal.
For the meter, use either a full-scale 0-1mAdc ammeter or full-scale 0-7.5Vdc (or 10Vdc-1mA) voltmeter.
Switching to 0-20mAdc (4-20mAdc) output current can be made by turning the FM (SW2) slide switch to
the I position. When switching to 4-20mAdc current input, make adjustments using H (analog
output gradient) and H (analog output bias).

[Parameter setting]

Title

Function

Adjustment range

Supposition output at

HOUN

=

Default setting

0: Output frequency

Maximum frequency (HJ)

1: Output current

1.5 times of rated current

2: Set frequency

Maximum frequency (HJ)

3: DC voltage

1.5 times of rated voltage

4: Output voltage command value

1.5 times of rated voltage

5: Input power

1.85 times of rated power

6: Output power

1.85 times of rated power

7: Torque

2.5 times of rated torque

8: Torque current

2.5 times of rated torque

9: Motor cumulative load factor

Rated load factor

10: Inverter cumulative load factor
11: - (Do not select)

Rated load factor

-

12: Frequency setting value (after PID)

Maximum frequency (HJ)

13: VIA Input value

Maximum input value

14: VIB Input value

Maximum input value

15: Fixed output 1 (Output current: 100%)

-

16: Fixed output 2 (Output current: 50%)

-

17: Fixed output 3

(Supposition output at HOUN=17)

-

18: Serial communication data

FA51=1000

HOUN

Meter
selection

19: For adjustments (HOset value is

displayed.)

-

0

HO

Meter
adjustment

-

-

-