(2) A signal is sent out when either of the two functions assigned is activated.
Terminal
symbol
Title
Function
Adjustment range
Default setting
RY - RC
H
Output terminal selection 1A
4 (Low-speed
detection signal)
RY - RC
H
Output terminal selection 1B
0~255
(
⇒ See page K-17)
255 (Always ON)
0 : H and H
RY - RC
H
Output terminal logic selection
1 : H or H
0
+
Two different functions can be assigned to terminals RY-RC.
+
If parameter H is set to , a signal will be sent out when either of the two functions assigned is
activated.
Terminals RY-RC: Send out a signal when either of the functions set with H and H is activated.
+
Timing chart
ON
OFF
ON
OFF
ON
OFF
H
H
RY-RC output
+
Only one function can be assigned to terminals FLA-FLB-FLC at a time.
(3) Holding the output of signals in ON status
+
If the conditions for activating the functions assigned to output terminals RY-RC agree with and as a result
the output of signals is put in ON status, the output of signals is held ON, even if the conditions change.
(Output terminal holding function)
+
Assign input terminal function 62 to a contact input terminal available.
■
Input terminal function
Function No.
Code
Function
Action
62
HDRY
Holding of RY-RC terminal
output
ON: Once turned on, RY-RC is held on.
OFF: The status of RY-RC changes in real
time according to conditions.
+
Once output terminal RY-RC is turned on when the contact input terminal to which one of the above
functions (function 62) is assigned is ON, output terminal RY-RC is held ON.