Toshiba VF-FS1 User Manual

Page 107

background image

E6581381

F-11

6

(2) A signal is sent out when either of the two functions assigned is activated.

Terminal

symbol

Title

Function

Adjustment range

Default setting

RY - RC

H

Output terminal selection 1A

4 (Low-speed

detection signal)

RY - RC

H

Output terminal selection 1B

0~255

(

⇒ See page K-17)

255 (Always ON)

0 : H and H

RY - RC

H

Output terminal logic selection

1 : H or H

0

+

Two different functions can be assigned to terminals RY-RC.

+

If parameter H is set to , a signal will be sent out when either of the two functions assigned is
activated.
Terminals RY-RC: Send out a signal when either of the functions set with H and H is activated.

+

Timing chart

ON

OFF

ON

OFF

ON

OFF

H

H

RY-RC output

+

Only one function can be assigned to terminals FLA-FLB-FLC at a time.

(3) Holding the output of signals in ON status

+

If the conditions for activating the functions assigned to output terminals RY-RC agree with and as a result
the output of signals is put in ON status, the output of signals is held ON, even if the conditions change.
(Output terminal holding function)

+

Assign input terminal function 62 to a contact input terminal available.

Input terminal function

Function No.

Code

Function

Action

62

HDRY

Holding of RY-RC terminal
output

ON: Once turned on, RY-RC is held on.
OFF: The status of RY-RC changes in real

time according to conditions.

+

Once output terminal RY-RC is turned on when the contact input terminal to which one of the above
functions (function 62) is assigned is ON, output terminal RY-RC is held ON.