6 operation frequency, 1 starting frequency, 2 run/stop control with frequency setting signals – Toshiba VF-FS1 User Manual
Page 118

E6581381
F-22
6
6.6
Operation frequency
6.6.1 Starting frequency
H
: Starting frequency setting
• Function
The frequency set with H is put out as soon as operation is started.
Use the H parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Starting frequency setting
0.5-10.0 (Hz)
0.5
6.6.2 Run/stop control with frequency setting signals
H
: Operation starting frequency
H
: Operation starting frequency hysteresis
• Function
The Run/stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Operation starting frequency
0.0-HJ (Hz)
0.0
H
Operation starting frequency hysteresis
0.0-HJ (Hz)
0.0
0
A
B
100% Frequency command value
H
+ H
H
H
- H
HJ
The inverter begins accelerating after
the frequency setting signal has reached
point B.
Deceleration begins when the frequency
setting signal decreases below point A.
Output frequency [Hz]