F-22

6

6.6

Operation frequency

6.6.1 Starting frequency

H

: Starting frequency setting

• Function

The frequency set with H is put out as soon as operation is started.
Use the H parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Starting frequency setting

0.5-10.0 (Hz)

0.5

6.6.2 Run/stop control with frequency setting signals

H

: Operation starting frequency

H

: Operation starting frequency hysteresis

• Function

The Run/stop of operation can be controlled simply with frequency setting signals.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Operation starting frequency

0.0-HJ (Hz)

0.0

H

Operation starting frequency hysteresis

0.0-HJ (Hz)

0.0

0

A

B

100% Frequency command value

H

+ H

H

H

- H

HJ

The inverter begins accelerating after
the frequency setting signal has reached
point B.
Deceleration begins when the frequency
setting signal decreases below point A.

Output frequency [Hz]