Table of input terminal functions 1

Function

No.

Code

Function

Action

0

-

No function is assigned

Disabled

1

ST

Standby terminal

ON: Ready for operation
OFF: Coast stop (gate off)

2

F

Forward run command

ON: Forward run OFF: Slowdown stop

3

R

Reverse run command

ON: Reverse run OFF: Slowdown stop

5

AD2

Acceleration/deceleration 2 pattern selection

ON: Acceleration/deceleration 2
OFF: Acceleration/deceleration 1 or 3

6

SS1

Preset-speed command 1

7

SS2

Preset-speed command 2

8

SS3

Preset-speed command 3

Selection of 7-speed with SS1 to SS3 (3bits)

10

RES

Reset command

ON: Acceptance of reset command
ON

→ OFF: Trip reset

11

EXT

Trip stop command from external input device

ON: G Trip stop

13

DB

DC braking command

ON: DC braking

14

PID

PID control prohibited

ON: PID control prohibited
OFF: PID control permitted

15

PWENE

Permission of parameter editing

ON: Parameter editing permitted
OFF: Parameter editing prohibited (If H = )

16

ST+RES

Combination of standby and reset commands

ON: Simultaneous input from ST and RES

20

F+AD2

Combination of forward run and
acceleration/deceleration 2

ON: Simultaneous input from F and AD2

21

R+AD2

Combination of reverse run and
acceleration/deceleration 2

ON: Simultaneous input from R and AD2

22

F+SS1

Combination of forward run and preset-speed
command 1

ON: Simultaneous input from F and SS1

23

R+SS1

Combination of reverse run and preset-speed
command 1

ON: Simultaneous input from R and SS1

24

F+SS2

Combination of forward run and preset-speed
command 2

ON: Simultaneous input from F and SS2

25

R+SS2

Combination of reverse run and preset-speed
command 2

ON: Simultaneous input from R and SS2

26

F+SS3

Combination of forward run and preset-speed
command 3

ON: Simultaneous input from F and SS3

27

R+SS3

Combination of reverse run and preset-speed
command 3

ON: Simultaneous input from R and SS3

30

F+SS1+AD2

Combination of forward run, preset-speed
command 1 and acceleration/deceleration 2

ON: Simultaneous input from F, SS1 and AD2

31

R+SS1+AD2

Combination of reverse run, preset-speed
command 1 and acceleration/deceleration 2

ON: Simultaneous input from R, SS1 and AD2

32

F+SS2+AD2

Combination of forward run, preset-speed
command 2 and acceleration/deceleration 2

ON: Simultaneous input from F, SS2 and AD2

33

R+SS2+AD2

Combination of reverse run, preset-speed
command 2 and acceleration/deceleration 2

ON: Simultaneous input from R, SS2 and AD2

34

F+SS3+AD2

Combination of forward run, preset-speed
command 3 and acceleration/deceleration 2

ON: Simultaneous input from F, SS3 and AD2

35

R+SS3+AD2

Combination of reverse run, preset-speed
command 3 and acceleration/deceleration 2

ON: Simultaneous input from R, SS3 and AD2

38

FCHG

Frequency command forced switching

ON: H (If H = )
OFF: HOQF

39

VF2

No.2 Switching of V/F setting

ON: No.2 V/F setting

(RV=0, H, H, H, H)

OFF: No.1 V/F setting

(Set value of RV, XN, XNX, XD, VJT)

40

MOT2

No.2 motor switching

VF2+AD2+OCS2)

ON: No.2 motor

(RV=0, H, H, H, H,
H

, H, H, H)

OFF: No.1 motor (Set value of RV, XN, XNX,

XD

, VJT, CEE, FGE, H, H)

41

UP

Frequency UP signal input from external contacts

ON: Increase in frequency

42

DOWN

Frequency DOWN signal input from external
contacts

ON: Reduction in frequency