• Output parameters

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

H

0691

Inclination
characteristic of
analog output

-

-

0: Negative inclination (downward

slope)

1: Positive inclination (upward slope)

1

6.19.1

H

0692

Bias of analog
output

%

1/1

0-100

0

• Operation panel parameters

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

H

0700

Prohibition of
parameter change

-

-

0: Permitted
1: Prohibited

0

6.20.1

H

0701

Current/voltage
display mode

-

-

0: %
1: A (ampere)/V (volt)

0

6.20.2

H

0702

Frequency free
unit magnification

Times

0.01/0.01

0.00: Free unit display disabled

(display of frequency)

0.01-200.0

0.00

H

0705

Inclination
characteristic of
free unit display

-

-

0: Negative inclination (downward

slope)

1: Positive inclination (upward slope)

1

H

0706

Bias of free unit
display

Hz

0.01/0.01

0.00-HJ

0.00

6.20.3

H

0707

Free step 1
(pressing a panel
key once)

Hz

0.01/0.01

0.00: Disabled
0.01-HJ

0.00

H

0708

Free step 2 (panel
display)

-

1/1

0: Disabled
1-255

0

6.20.4

H

0710

Standard monitor
display selection

-

-

0: Operation frequency (Hz/free

unit/step)

1: Frequency command (Hz/free

unit/step)

2: Output current (%/A)
3: Inverter rated current (A)
4: Inverter load factor (%)
5: Output power (kW)
6: Frequency command after PID

control (Hz/free unit/step)

7: Optional item specified from an

external control unit

8: Output speed
9: Communication counter
10: Normal state communication

counter

0

6.20.5

H

0721

Selection of
operation panel
stop pattern

-

-

0: Slowdown stop
1: Coast stop

0

6.20.6

H

0730

Prohibition of
frequency setting
on the operation
panel (HE)

-

-

0: Permitted
1: Prohibited

0

6.20.1

H

0732

Prohibition of
panel local/remote
operation
(LOC/REM key)

-

-

0: Permitted
1: Prohibited

0

H

0733

Prohibition of
panel operation
(RUN/STOP keys)

-

-

0: Permitted
1: Prohibited

0