Toshiba VF-FS1 User Manual
Page 218

E6581381
K-10
11
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0609
Small current
detection current
hysteresis
%
1/1
1-20
10
H
0610
Small current
trip/alarm
selection
-
-
0: Alarm only
1: Tripping
0
H
0611
Small current
detection current
%
(A)
1/1
0-100
0
H
0612
Small current
detection time
s
1/1
0-255
0
6.17.7
H
0613
Detection of
output short-circuit
during start-up
-
-
0: Each time (standard pulse)
1: Only one time after power is turned
on (standard pulse)
2: Each time (short-time pulse)
3: Only one time after power is turned
on (short-time pulse)
0
6.17.8
H
0615
Over-torque
trip/alarm
selection
-
-
0: Alarm only
1: Tripping
0
H
0616
Over-torque
detection level
%
1/1
0-200
130
H
0618
Over-torque
detection time
s
0.1/0.1
0.0-10.0
0.5
6.17.9
H
0619
Over-torque
detection level
hysteresis
%
1/1
0-100
10
H
0621
Cumulative
operation time
alarm setting
100
Time
0.1/0.1
(=10 hours)
0.0-999.9
610.0
6.17.10
H
0626
Overvoltage limit
operation level
%
1/1
100-150
140
6.12.4
H
0627
Undervoltage
trip/alarm
selection
-
-
0: Alarm only
(detection level below 60%)
1: Tripping
(detection level below 60%)
2: Alarm only
(detection level below 50%,
input reactor necessary)
0
6.17.12
H
0632
Thermal memory
selection
-
-
0: Disabled
1: Enabled
0
6.17.1
H
0633
Trip at VIA low
level input mode
%
1/1
0: Disabled, 1-100
0
6.17.13
H
0634
Annual average
ambient
temperature (For
parts replacement
alarms)
-
-
1: -10 to +10
°C
2: 11-20
°C
3: 21-30
°C
4: 31-40
°C
5: 41-50
°C
6: 51-60
°C
3
6.17.14
H
0645
PTC thermal
selection
-
-
0: Disabled
1: Enabled (trip mode)
2: Enabled (alarm mode)
0
6.17.15
H
0646
PTC detection
resistor value
Ω
1/1
100-9999
3000
H
0650
Forced fire-speed
control selection
-
-
0: Disabled
1: Enabled
0
6.18