beautypg.com

10 bumpless operation – Toshiba VF-FS1 User Manual

Page 122

background image

E6581381

F-26

6

6.10 Bumpless operation

H

: Bumpless operation selection

• Function

When switching from Remote mode to Local mode using key, the status of start and stop, and
operating frequency at Remote mode are moved to Local mode.
By contraries, when switching from Local mode to Remote mode, they are not moved to Remote
mode.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Bumpless operation selection

0: Disabled
1: Enabled

1

Example : Remote mode ( EOQF (Terminal board))

Remote mode

Local mode

ON
OFF

ON
OFF

ON
OFF

Key

Output
frequency

F-CC

Internal
operation
command

Local mode

Remote mode

ON
OFF

ON
OFF

ON
OFF

Key

Output
frequency

F-CC

Internal
operation
command

Set frequency at
Remote mode

Setting frequency and start/stop
status are moved to Local mode
when switching from Remote
mode to Local mode.
Motor runs continuously like an
example.

When switching from Local
mode to Remote mode, setting
frequency and start/stop status
are determined by Remote
mode status.
The example shows the motor
runs continuously because the
Remote mode is “run” status.

To prevent from moving the setting frequency and start/stop status of Remote mode to Local mode,
the H is set to “”(Disabled). In this case, key is effective only while stopping.

LOC

REM

LOC

REM

LOC

REM

LOC

REM