10. Peripheral devices

Danger

Mandatory

• When using switchgear for the inverter, it must be installed in a cabinet.

Failure to do so can lead to risk of electric shock and can result in death or serious injury.

Be Grounded

• Connect earth cables securely.

Failure to do so can lead to risk of electric shock or fire in case of a failure or short-circuit or electric
leak.

10.1 Selection of wiring materials and devices

Wire size (See Note 4)

Power circuit

(mm

2

) Note 1)

Earth cable

(mm

2

)

Voltage

class

Capacity of

applicable motor

(kW)

Inverter model

For IEC60364-5-

523/54

For JAPAN

JEAC8001-1995

For IEC60364-5-

523/54

For JAPAN

JEAC8001-1995

0.4

VFFS1-2004PM

1.5

2

2.5

2

0.75

VFFS1-2007PM

1.5

2

2.5

2

1.5

VFFS1-2015PM

1.5

2

2.5

2

2.2

VFFS1-2022PM

1.5

2

2.5

2

4.0

VFFS1-2037PM

2.5

2

2.5

2

5.5

VFFS1-2055PM

4

3.5

4

3.5

7.5

VFFS1-2075PM

6

5.5

6

3.5

11

VFFS1-2110PM

10

14

10

5.5

15

VFFS1-2150PM

16

14

16

5.5

18.5

VFFS1-2185PM

25

22

16

8

22

VFFS1-2220PM

25

38

16

8

Three-phase
200V class

30

VFFS1-2300PM

50

38

25

14

0.4

VFFS1-4004PL

1.5

2

2.5

2

0.75

VFFS1-4007PL

1.5

2

2.5

2

1.5

VFFS1-4015PL

1.5

2

2.5

2

2.2

VFFS1-4022PL

1.5

2

2.5

2

4.0

VFFS1-4037PL

1.5

2

2.5

2

5.5

VFFS1-4055PL

1.5

2

2.5

2

7.5

VFFS1-4075PL

1.5

2

2.5

2

11

VFFS1-4110PL

4

3.5

4

3.5

15

VFFS1-4150PL

6

5.5

6

3.5

18.5

VFFS1-4185PL

6

5.5

6

5.5

22

VFFS1-4220PL

10

8

10

5.5

Three-phase
400V class

30

VFFS1-4300PL

16

14

16

5.5

Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 and the output terminals U/T1,

V/T2 and W/T3 when the length of each wire does not exceed 30m.

Note 2: For the control circuit, use shielded wires 0.75 mm

2

or more in diameter.

Note 3: For grounding, use a cable with a size equal to or larger than the above.
Note 4: The wire sizes specified in the above table apply to HIV wires (cupper wires shielded with an insulator

with a maximum allowable temperature of 75°C) used at an ambient temperature of 40°C or less.

Note 5: If there is a need to bring the inverter into UL compliance, use wires specified in Chapter 9.