20 operation panel parameter – Toshiba VF-FS1 User Manual

Page 166

background image

E6581381

F-70

6

6.20 Operation panel parameter

6.20.1 Prohibition of key operations and parameter settings

H

: Prohibition of parameter change

H

: Prohibition of frequency setting on the operation panel (FC)

H

: Prohibition of panel local/remote operation (LOC/REM key)

H

: Prohibition of panel operation (RUN/STOP keys)

H

: Prohibition of panel emergency stop operation

H

: Prohibition of panel reset operation

• Function

These parameters allow you to prohibit the operation of the RUN and STOP keys on the operation
panel and the change of parameters. Using these parameters, you can also prohibit various key
operations.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Prohibition of parameter change

0: Permitted, 1: Prohibited

0

H

Prohibition of frequency setting on the
operation panel (FC)

0: Permitted, 1: Prohibited

0

H

Prohibition of panel local/remote
operation (LOC/REM key)

0: Permitted, 1: Prohibited

0

H

Prohibition of panel operation
(RUN/STOP keys)

0: Permitted, 1: Prohibited

0

H

Prohibition of panel emergency stop
operation

0: Permitted, 1: Prohibited

0

H

Prohibition of panel reset operation

0: Permitted, 1: Prohibited

0

Resetting method

Only the H parameter is designed so that its setting can be modified even if 1 (prohibited) is selected.