Operation mode parameters – Toshiba VF-FS1 User Manual
Page 214

E6581381
K-6
11
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0266
External contact
input - DOWN
response time
s
0.1/0.1
0.0-10.0
0.1
6.5.3
H
0267
External contact
input - DOWN
frequency steps
Hz
0.1/0.01
0.0-HJ
0.1
H
0268
Initial UP/DOWN
frequency
Hz
0.1/0.01
NNWN
0.0
H
0269
Change of the
initial up/down
frequency
-
-
0: Not changed
1: Setting of H changed when
power is turned off
1
H
0270
Jump frequency 1
Hz
0.1/0.01
0.0-HJ
0.0
6.9
H
0271
Jumping width 1
Hz
0.1/0.01
0.0-30.0
0.0
H
0272
Jump frequency 2
Hz
0.1/0.01
0.0-HJ
0.0
H
0273
Jumping width 2
Hz
0.1/0.01
0.0-30.0
0.0
H
0274
Jump frequency 3
Hz
0.1/0.01
0.0-HJ
0.0
H
0275
Jumping width 3
Hz
0.1/0.01
0.0-30.0
0.0
H
0294
Forced fire-speed
setting frequency
Hz
0.1/0.01
NN
-WN
50.0
6.18
H
0295
Bumpless
operation
selection
-
-
0: Disabled
1: Enabled
1
6.10
• Operation mode parameters
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0300
PWM carrier
frequency
kHz
0.1/0.1
6.0 - 16.0
* 1
6.11
H
0301
Auto-restart
control selection
-
-
0: Disabled
1: At auto-restart after momentary
stop
2: When turning ST-CC on or off
3: At auto-restart or when turning ST-
CC on or off
4: At start-up
0
6.12.1
H
0302
Instantaneous
power failure
coast stop
selection
-
-
0: Disabled
1: - (Do not select)
2: Coast stop
0
6.12.2
H
0303
Retry selection
(number of times)
Times
1/1
0: Disabled
1-10
0
6.12.3
H
0305
Overvoltage limit
operation
(Slowdown stop
mode selection)
-
-
0: Enabled
1: Disabled
2: Enabled (Quick deceleration)
3: Enabled (Dynamic quick
deceleration)
2
6.12.4