E6581381

E-8

5

EOQF

: Command mode selection

HOQF

: Frequency setting mode selection 1

• Function

Remote mode selection, these parameters are used to specify which input device (operation panel,
terminal board, serial communication) takes priority in entering an operation stop command or a frequency
setting command, VIA, VIB, operation panel, serial communication device, external contact up/down).
At Local mode selection, the start/stop operation and frequency setting by operation panel is prior with no
relation of EOQF/HOQFsetting.

Title

Function

Adjustment range

Default setting

EOQF

Command mode selection

0: Terminal board
1: Operation panel
2: Serial communication

0

Programmed value

:

Terminal board
operation

ON and OFF of an external signal Runs and stops operation.

:

Operation panel
operation

Press the and keys on the operation panel to start and stop.

Serial communication
operation

Run and stop through serial communication.

* There are two types of function: the function that conforms to commands selected by EOQF, and the function

that conforms only to commands from the terminal board.
⇒ See the table of input terminal function selection in Chapter 11.

* When priority is given to commands from a linked computer or terminal board, they have priority over the

setting of EOQF.

STOP

RUN