6.8

Auto-stop in case of lower-limit frequency continuous
operation

6.8.1 Auto-stop in case of lower-limit frequency continuous

operation

H

: Auto-stop in case of lower-limit frequency continuous operation

• Function

If operation is carried out continuously at a frequency command below the lower-limit frequency (NN) for
the period of time set with H, the inverter will automatically slow down the motor to a stop. At that
time, “NUVR” is displayed (alternately) on the operation panel.
This function will be canceled if a frequency command above the lower-limit frequency (NN) +0.2Hz.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Auto-stop in case of lower-limit
frequency continuous operation time

0.0: Disabled
0.1-600.0 (s)

0.0

Note: This function is enabled even at the start of operation and during switching between forward and

reverse run.

Output frequency [Hz]

NN

+0.2Hz

NN

Operation signal (F or R)

Time [s]

H

ON
OFF

H

H