Toshiba VF-FS1 User Manual

Page 194

background image

E6581381

H-8

8

(Continued)

Item displayed

Key

operated

LED

display

Communic

ation No.

Description

Integral output
power

J

FE77

The integrated amount of power (kWh) supplied
from the inverter is displayed.
(0.01=1kWh, 1.00=100kWh)

Rated current

C

FE70

The inverter rated current (A) at the occurrence of
a trip is displayed.

Output speed

FE90

Displays the motor speed ( min-1) by calculating
with output frequency and pole numbers.

Communication
counter

O

FA15

Displays the counter numbers of communication
through the network.
Note that they are current values, not at tripping.

Normal state
communication
counter

P

FA16

Displays the counter numbers of communication
only at normal state in the all communication
through network.
Note that they are current values, not at tripping.

Past trip 1

QR

FE10

Past trip 1 (displayed alternately)

Past trip 2

QJ

FE11

Past trip 2 (displayed alternately)

Past trip 3

QR

FE12

Past trip 3 (displayed alternately)

Past trip 4

PGTT

FE13

Past trip 4 (displayed alternately)

Parts replacement
alarm information

O___K

FE79

The ON/OFF status of each of the cooling fan,
circuit board capacitor, main circuit capacitor of
parts replacement alarm or cumulative operation
time are displayed in bits.

ON:
OFF: _

Cumulative
operation time

V

FE14

The cumulative operation time is displayed.
(0.01=1 hour, 1.00=100 hours)

Default display
mode

QR

The cause of the trip is displayed.

Note 1: Items displayed can be changed by pressing or key in the each monitor mode.

Note 2: You can switch between % and A (ampere)/V (volt), using the parameter H (current/voltage unit

selection).

Note 3: The input (DC) voltage displayed is 1

2 times as large as the rectified d.c. input voltage.

Note 7

Note 8

Note 6

Note 6

Note 6

Note 6

O

___K

Cooling fan

operation time

Control circuit board capacitor
Main circuit capacitor

MODE