6.17.9 Over-torque trip
H
: Over-torque trip/alarm selection
H
: Over-torque detection level
H
: Over-torque detection time
H
: Over-torque detection level hysteresis
• Function
Use the parameter to trip the inverter or to output the alarm if a torque currrent exceeding the
H
-specified level flows for more than the H-specified time. Trip information is displayed
as "QV".
H
=: .......... No tripping (FL relay deactivated).
An over-torque alarm can be put out by setting the output terminal function selection
parameter.
H
=: .......... The inverter is tripped (FL relay activated) only after a torque current exceeding the
H
-specified level has been detected for more than the H-specified time.
Title
Function
Adjustment range
Default setting
H
Over-torque trip/alarm selection
0: Alarm only
1: Tripping
0
H
Over-torque detection level
0-200 (%)
130
H
Over-torque detection time
0.0-10.0 [s]
0.5
H
Over-torque detection level hysteresis
0-100 (%)
10