9 over-torque trip – Toshiba VF-FS1 User Manual

Page 157

background image

E6581381

F-61

6

Title

Function

Adjustment range

Default setting

H

Detection of output short-circuit during
start-up

0: Each time (standard pulse)
1: Only one time after power is

turned on (standard pulse)

2: Each time (short-time pulse)
3: Only one time after power is

turned on (short-time pulse)

0

6.17.9 Over-torque trip

H

: Over-torque trip/alarm selection

H

: Over-torque detection level

H

: Over-torque detection time

H

: Over-torque detection level hysteresis

• Function

Use the parameter to trip the inverter or to output the alarm if a torque currrent exceeding the
H

-specified level flows for more than the H-specified time. Trip information is displayed

as "QV".

H

=: .......... No tripping (FL relay deactivated).

An over-torque alarm can be put out by setting the output terminal function selection
parameter.

H

=: .......... The inverter is tripped (FL relay activated) only after a torque current exceeding the

H

-specified level has been detected for more than the H-specified time.

Title

Function

Adjustment range

Default setting

H

Over-torque trip/alarm selection

0: Alarm only
1: Tripping

0

H

Over-torque detection level

0-200 (%)

130

H

Over-torque detection time

0.0-10.0 [s]

0.5

H

Over-torque detection level hysteresis

0-100 (%)

10